Marley
LW Fluid Cooler
Full specifications
| Access Doors per Cell | 6–10 (gasketless, tool-free removable) | ↗ |
| Certifications | CTI Certified, ASHRAE 90.1, OSHA | ↗ |
| Coil Material | Copper (30–40% lighter than galvanized steel alternatives) | ↗ |
| Collection Basin | Bolted stainless steel (standard) | ↗ |
| Configuration | Induced Draft Counterflow Fill/Coil Hybrid | ↗ |
| Fan Drive | ECM (integral speed control); or AC motor direct drive (LWA models) | ↗ |
| Flow Rate | 20–1,200 gpm per cell | ↗ |
| Maximum Unit Height | Less than 10.5 ft | ↗ |
| Spray Nozzle Orifice | 1-7/8 in | ↗ |
| Thermal Capacity | 26–107 tons per cell | ↗ |
Every figure is traced to the manufacturer’s published data. ↗ opens the source.
Export for Heyquip
Populate your Heyquip store's product page with this model's specs, images, and cited documents.
Is this your equipment? Verify your specs →