Distribution Panel
A portable distribution panel is the branch-circuit hub of a temporary power system: an enclosure that accepts a feeder from a generator or service, protects outgoing circuits with breakers, and hands power off through receptacles or sub-feed connections. Panels convert one large feed into the many protected circuits a site actually uses.

Fonctionnement
Feeder power enters through cam-type inlets, hardwired lugs, or a cord, landing on a main breaker or lugs. From there, branch breakers protect individual circuits terminating in receptacles — commonly a mix of straight-blade duplexes for tools and twist-lock or pin-and-sleeve outlets for equipment and sub-feeds. Construction-grade panels build in the protections temporary power demands: GFCI on receptacle circuits, weather-resistant enclosures with covers, and skids, stands, or hanging brackets that keep the panel out of water and traffic.
Types et variantes
- Portable panelboards
- Free-standing or skid-mounted panels distributing a generator or service feed into multiple protected branch circuits.
- Temporary power boxes
- Compact cord-connected boxes bringing a few protected receptacle circuits to a work area.
- Sub-feed and stringer panels
- Panels designed to daisy-chain, passing the feeder through while dropping protected circuits along a route.
- Hazardous-location distribution
- Certified distribution assemblies for classified areas in industrial and plant work.
Spécifications clés
| Spécification | Plage typique | Signification |
|---|---|---|
| System voltage | 120/240 V single-phase and 208Y/120 V or 480 V three-phase nominal, configuration dependent | The panel's voltage configuration must match the source and the loads; mixed-voltage panels also host step-down connections. |
| Branch protection | Thermal-magnetic breakers with GFCI on receptacle circuits | Breakers protect conductors; GFCI protects people — required on construction receptacle circuits. |
| Feeder inlet | Cam-type inlets, pin-and-sleeve inlets, or lugs, model dependent | Determines how the panel connects to the feeder system and how quickly services assemble. |
| Enclosure rating | Weather-resistant enclosures on outdoor-rated panels, model dependent | Temporary panels live outdoors in traffic; the enclosure rating must match the exposure. |
Comment l'industrie le dimensionne
Panels are sized from the branch-circuit map: enough breaker positions and receptacle types for the tools and equipment served, a main rating that covers the connected demand, and a voltage configuration matching the source. Large sites layer panels — feeder-level panels near the generator sub-feeding smaller boxes at work areas — keeping cord runs short and protection close to the load.
Applications
- Distributing generator power into protected tool circuits on construction sites
- Temporary building services during renovation and fit-out
- Event and production power distribution to vendors and stages
- Plant shutdown and turnaround temporary power
- Powering trailers, hoists, and fixed equipment through sub-feeds
Sécurité et opération
- Receptacle circuits serving portable tools on construction sites require GFCI protection per OSHA and NEC Article 590.
- Keep enclosure covers closed and cord entries fitted; open panels expose energized parts to weather and contact.
- Mount panels above standing water and out of vehicle paths, on their skids, stands, or hangers.
- Verify grounding and bonding continuity back to the source before energizing; a floating panel ground defeats every downstream protection.
- Only qualified persons should open panels or alter breaker configurations.
Normes et certifications
- UL · UL 1640
- Safety standard for portable power-distribution equipment.
- NFPA · NFPA 70 (NEC), Article 590
- Temporary installation rules including GFCI requirements for receptacle circuits.
- OSHA · 29 CFR 1926.404(b)(1)
- Ground-fault protection requirements for receptacle outlets on construction sites.
Questions fréquentes
What distinguishes a portable distribution panel from a building panelboard?
Does every circuit on a temporary panel need GFCI?
How many panels does a site need?
Équipements connexes
Parcourir par fabricant
Sources
Chaque spécification est vérifiée par rapport aux données publiées par le fabricant, avec la source liée pour référence.
Tous les modèles
19 modèles · Chaque spécification citée à la source